{"id":10189,"date":"2019-03-05T09:10:51","date_gmt":"2019-03-05T14:10:51","guid":{"rendered":"https:\/\/www.est-aegis.com\/?p=155"},"modified":"2026-10-22T14:52:03","modified_gmt":"2026-10-22T18:52:03","slug":"reliable-data-center-cooling","status":"publish","type":"post","link":"https:\/\/www.est-aegis.com\/de\/blog\/reliable-data-center-cooling\/","title":{"rendered":"Reliable Data Center Cooling Requires Motor Bearing Protection"},"content":{"rendered":"\n<p class=\"wp-block-paragraph\">Variable frequency drives (VFDs) are widely used in data center cooling applications because they offer precise control of motor speed and significant energy savings.\u00a0 Without variable speed control, a motor can either run at full speed or not at all.\u00a0 Most applications don&#8217;t need constant full-speed motor operation, so that wastes energy.\u00a0 With VFD control, though, motors are run only as fast as the situation demands.\u00a0 In HVAC applications, this can give energy savings of up to 30%.\u00a0 And 30% of the power for a data center&#8217;s cooling amounts to a lot of money saved.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><img loading=\"lazy\" decoding=\"async\" class=\"alignright\" alt=\"dc-applications\" height=\"238\" src=\"https:\/\/www.est-aegis.com\/wp-content\/uploads\/dc-applications.jpg\" width=\"300\"><\/p>\n\n\n\n<p class=\"wp-block-paragraph\">But though savings are great, they aren&#8217;t everything.\u00a0 Reliability is even more important in a data center.\u00a0 And VFDs are unfortunately bad for motor reliability.\u00a0 To start with, they can burn out the windings of motors with low-grade insulation.\u00a0 Nowadays, though, most motors come with inverter-ready or inverter-duty winding insulation, which can tolerate the stresses of VFD control.\u00a0 But winding damage isn&#8217;t the only risk of VFD control.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">VFDs can also destroy the bearings of the motors they control.\u00a0 They do this by generating a voltage between the motor&#8217;s rotor and stator frame.\u00a0 This so-called shaft voltage tends to discharge or arc through the motor bearings.\u00a0 This arcing can occur thousands of times per second, and every arc leaves an invisibly tiny crater behind.\u00a0 Over time, these craters accumulate and roughen the smooth surfaces of the bearing. This causes noise, vibration, and eventual bearing failure.\u00a0 The bearings of motors on VFDs can sometimes fail in only a few months.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">When a bearing has failed, there are two options.\u00a0 You can replace the bearing, or just buy a new motor.\u00a0 Neither option is especially cheap.\u00a0 And one data center might have hundreds of motors under VFD control.\u00a0 The costs can add up fast, and even cancel out the energy savings from using VFDs.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Clearly, some form of bearing protection is needed.\u00a0 One way to protect the bearings is to ground the shaft with a low-resistance brush.\u00a0 Charge preferentially flows through the device instead of through a bearing.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><img loading=\"lazy\" decoding=\"async\" class=\"alignright\" alt=\"family\" height=\"104\" src=\"https:\/\/www.est-aegis.com\/wp-content\/uploads\/family.webp\" width=\"300\"><\/p>\n\n\n\n<p class=\"wp-block-paragraph\">One popular and effective shaft grounding device is the AEGIS Shaft Grounding Ring.\u00a0 AEGIS rings surround the motor shaft with hundreds of thousands of conductive microfibers.\u00a0 The microfibers bleed off shaft voltage before it builds up enough to arc through the bearings.\u00a0 AEGIS rings work in most environments without maintenance or appreciable wear.\u00a0 Testing has shown that they wear only 0.001&#8243; in 10,000 hours of operation.\u00a0 Extrapolating, gives the grounding rings an operating lifetime of 200,000 hours.\u00a0 That&#8217;s about twice the L10 lifetime of a typical bearing.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">With AEGIS rings installed, VFD-fed motors are safe from electrical bearing damage.\u00a0 By using AEGIS rings, data centers can reap the savings promised by VFDs, without the risk of unexpected repair and replacement costs.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><img loading=\"lazy\" decoding=\"async\" class=\"alignright\" alt=\"Motors-with-AEGIS-Inside-1\" height=\"176\" src=\"https:\/\/www.est-aegis.com\/wp-content\/uploads\/Motors-with-AEGIS-Inside-1.jpg\" width=\"300\"><\/p>\n\n\n\n<p class=\"wp-block-paragraph\">AEGIS rings can easily be installed externally.\u00a0 But since they last so long and rarely need maintenance, they can also be installed inside motors.\u00a0 Internal installation protects the rings from contamination and makes them even more reliable.\u00a0 And buying a new motor with AEGIS installed is the easiest way to get protection.\u00a0<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Several major motor manufacturers have lines of stock motors with AEGIS rings installed internally. These include Baldor-Reliance, WEG, Marathon, LEESON, and US Motors Varitough\u2122 condenser motors.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">To learn more about AEGIS shaft grounding and best practices for electrical bearing protection, <a href=\"https:\/\/www.est-aegis.com\/resources\/training\/\" rel=\"noopener\" target=\"_blank\">sign up for a training<\/a>. We offer monthly live training webinars, and &#8211; pandemic restrictions permitting &#8211; we can also visit your facility to review your exact application.<\/p>\n\n\n\n<div class=\"wp-block-buttons is-content-justification-center is-layout-flex wp-container-core-buttons-is-layout-fe48e5de wp-block-buttons-is-layout-flex\">\n<div class=\"wp-block-button\"><a class=\"wp-block-button__link wp-element-button\" href=\"https:\/\/www.est-aegis.com\/resources\/training\/\">Sign Up For Training<\/a><\/div>\n<\/div>\n\n","protected":false},"excerpt":{"rendered":"<p>Variable frequency drives (VFDs) are used in data center cooling, due to the energy savings they offer.  But VFDs can cause electrical bearing damage&#8230;<\/p>\n","protected":false},"author":7,"featured_media":1192,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"content-type":"","_relevanssi_hide_post":"","_relevanssi_hide_content":"","_relevanssi_pin_for_all":"","_relevanssi_pin_keywords":"","_relevanssi_unpin_keywords":"","_relevanssi_related_keywords":"","_relevanssi_related_include_ids":"","_relevanssi_related_exclude_ids":"","_relevanssi_related_no_append":"","_relevanssi_related_not_related":"","_relevanssi_related_posts":"","_relevanssi_noindex_reason":"","footnotes":""},"categories":[1064],"tags":[],"class_list":["post-10189","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-applications-and-industries"],"acf":[],"aioseo_notices":[],"aioseo_head":"\n\t\t<!-- All in One SEO Pro 5.0.5.1 - aioseo.com -->\n\t<meta name=\"description\" content=\"Variable frequency drives (VFDs) are used in data center cooling, due to the energy savings they offer. But VFDs can cause electrical bearing damage...\" \/>\n\t<meta name=\"robots\" content=\"noindex, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n\t<meta name=\"author\" content=\"AEGIS\"\/>\n\t<link rel=\"canonical\" href=\"https:\/\/www.est-aegis.com\/de\/blog\/reliable-data-center-cooling\/\" \/>\n\t\t<meta name=\"generator\" content=\"All in One SEO Pro (AIOSEO) 5.0.5.1\" \/>\n\t\t<meta property=\"og:locale\" content=\"de_DE\" \/>\n\t\t<meta property=\"og:site_name\" content=\"Electro Static Technology\" \/>\n\t\t<meta property=\"og:type\" content=\"article\" \/>\n\t\t<meta property=\"og:title\" content=\"Reliable Data Center Cooling Requires Motor Bearing Protection\" \/>\n\t\t<meta property=\"og:description\" content=\"Variable frequency drives (VFDs) are used in data center cooling, due to the energy savings they offer. But VFDs can cause electrical bearing damage...\" \/>\n\t\t<meta property=\"og:url\" content=\"https:\/\/www.est-aegis.com\/de\/blog\/reliable-data-center-cooling\/\" \/>\n\t\t<meta property=\"og:image\" content=\"https:\/\/www.est-aegis.com\/wp-content\/uploads\/dc-applications-300x238-1.jpg\" \/>\n\t\t<meta property=\"og:image:secure_url\" content=\"https:\/\/www.est-aegis.com\/wp-content\/uploads\/dc-applications-300x238-1.jpg\" \/>\n\t\t<meta property=\"og:image:width\" content=\"300\" \/>\n\t\t<meta property=\"og:image:height\" content=\"238\" \/>\n\t\t<meta property=\"article:published_time\" content=\"2019-03-05T14:10:51+00:00\" \/>\n\t\t<meta property=\"article:modified_time\" content=\"2026-10-22T18:52:03+00:00\" \/>\n\t\t<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n\t\t<meta name=\"twitter:site\" content=\"@AEGIS_rings\" \/>\n\t\t<meta name=\"twitter:title\" content=\"Reliable Data Center Cooling Requires Motor Bearing Protection\" \/>\n\t\t<meta name=\"twitter:description\" content=\"Variable frequency drives (VFDs) are used in data center cooling, due to the energy savings they offer. But VFDs can cause electrical bearing damage...\" \/>\n\t\t<meta name=\"twitter:creator\" content=\"@AEGIS_rings\" \/>\n\t\t<meta name=\"twitter:image\" content=\"https:\/\/www.est-aegis.com\/wp-content\/uploads\/dc-applications-300x238-1.jpg\" \/>\n\t\t<meta name=\"twitter:label1\" content=\"Verfasst von\" \/>\n\t\t<meta name=\"twitter:data1\" content=\"AEGIS\" \/>\n\t\t<meta name=\"twitter:label2\" content=\"Gesch\u00e4tzte Lesedauer\" \/>\n\t\t<meta name=\"twitter:data2\" content=\"3 Minuten\" \/>\n\t\t<script type=\"application\/ld+json\" class=\"aioseo-schema\">\n\t\t\t{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/blog\\\/reliable-data-center-cooling\\\/#article\",\"name\":\"Reliable Data Center Cooling Requires Motor Bearing Protection\",\"headline\":\"Reliable Data Center Cooling Requires Motor Bearing Protection\",\"author\":{\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/blog\\\/author\\\/aegis\\\/#author\"},\"publisher\":{\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/#organization\"},\"image\":{\"@type\":\"ImageObject\",\"url\":\"https:\\\/\\\/www.est-aegis.com\\\/wp-content\\\/uploads\\\/dc-applications-300x238-1.jpg\",\"width\":300,\"height\":238,\"caption\":\"#image_title\"},\"datePublished\":\"2019-03-05T09:10:51-05:00\",\"dateModified\":\"2026-10-22T14:52:03-04:00\",\"inLanguage\":\"de-DE\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/blog\\\/reliable-data-center-cooling\\\/#webpage\"},\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/blog\\\/reliable-data-center-cooling\\\/#webpage\"},\"articleSection\":\"Applications &amp; Industries, Optional\"},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/blog\\\/reliable-data-center-cooling\\\/#breadcrumblist\",\"itemListElement\":[{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/#listItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/\",\"nextItem\":{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/blog\\\/category\\\/applications-and-industries\\\/#listItem\",\"name\":\"Applications &amp; Industries\"}},{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/blog\\\/category\\\/applications-and-industries\\\/#listItem\",\"position\":2,\"name\":\"Applications &amp; Industries\",\"item\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/blog\\\/category\\\/applications-and-industries\\\/\",\"nextItem\":{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/blog\\\/reliable-data-center-cooling\\\/#listItem\",\"name\":\"Reliable Data Center Cooling Requires Motor Bearing Protection\"},\"previousItem\":{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/#listItem\",\"name\":\"Home\"}},{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/blog\\\/reliable-data-center-cooling\\\/#listItem\",\"position\":3,\"name\":\"Reliable Data Center Cooling Requires Motor Bearing Protection\",\"previousItem\":{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/blog\\\/category\\\/applications-and-industries\\\/#listItem\",\"name\":\"Applications &amp; Industries\"}}]},{\"@type\":\"Organization\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/#organization\",\"name\":\"Electro Static Technology\",\"url\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/\",\"logo\":{\"@type\":\"ImageObject\",\"url\":\"https:\\\/\\\/www.est-aegis.com\\\/wp-content\\\/uploads\\\/logo-aegis-1.svg\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/blog\\\/reliable-data-center-cooling\\\/#organizationLogo\",\"width\":244,\"height\":73,\"caption\":\"aegis logo\"},\"image\":{\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/blog\\\/reliable-data-center-cooling\\\/#organizationLogo\"},\"sameAs\":[\"https:\\\/\\\/x.com\\\/AEGIS_rings\"],\"address\":{\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/#postaladdress\",\"@type\":\"PostalAddress\",\"streetAddress\":\"31 Winterbrook Road\",\"postalCode\":\"04256\",\"addressLocality\":\"Mechanic Falls\",\"addressRegion\":\"ME\",\"addressCountry\":\"US\"}},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/blog\\\/author\\\/aegis\\\/#author\",\"url\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/blog\\\/author\\\/aegis\\\/\",\"name\":\"AEGIS\",\"image\":{\"@type\":\"ImageObject\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/blog\\\/reliable-data-center-cooling\\\/#authorImage\",\"url\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/8df5575541df78c551aa899db7bd2ee11bed27caea7dcd8c7695af230c7c1a04?s=96&d=mm&r=g\",\"width\":96,\"height\":96,\"caption\":\"AEGIS\"}},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/blog\\\/reliable-data-center-cooling\\\/#webpage\",\"url\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/blog\\\/reliable-data-center-cooling\\\/\",\"name\":\"Reliable Data Center Cooling Requires Motor Bearing Protection\",\"description\":\"Variable frequency drives (VFDs) are used in data center cooling, due to the energy savings they offer. But VFDs can cause electrical bearing damage...\",\"inLanguage\":\"de-DE\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/#website\"},\"breadcrumb\":{\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/blog\\\/reliable-data-center-cooling\\\/#breadcrumblist\"},\"author\":{\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/blog\\\/author\\\/aegis\\\/#author\"},\"creator\":{\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/blog\\\/author\\\/aegis\\\/#author\"},\"image\":{\"@type\":\"ImageObject\",\"url\":\"https:\\\/\\\/www.est-aegis.com\\\/wp-content\\\/uploads\\\/dc-applications-300x238-1.jpg\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/blog\\\/reliable-data-center-cooling\\\/#mainImage\",\"width\":300,\"height\":238,\"caption\":\"#image_title\"},\"primaryImageOfPage\":{\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/blog\\\/reliable-data-center-cooling\\\/#mainImage\"},\"datePublished\":\"2019-03-05T09:10:51-05:00\",\"dateModified\":\"2026-10-22T14:52:03-04:00\"},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/#website\",\"url\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/\",\"name\":\"Electro Static Technology\",\"inLanguage\":\"de-DE\",\"publisher\":{\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/de\\\/#organization\"}}]}\n\t\t<\/script>\n\t\t<!-- All in One SEO Pro -->\r\n\t\t<title>Reliable Data Center Cooling Requires Motor Bearing Protection<\/title>\n\n","aioseo_head_json":{"title":"Reliable Data Center Cooling Requires Motor Bearing Protection","description":"Variable frequency drives (VFDs) are used in data center cooling, due to the energy savings they offer. But VFDs can cause electrical bearing damage...","canonical_url":"https:\/\/www.est-aegis.com\/de\/blog\/reliable-data-center-cooling\/","robots":"noindex, max-snippet:-1, max-image-preview:large, max-video-preview:-1","keywords":"","webmasterTools":{"miscellaneous":""},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/www.est-aegis.com\/de\/blog\/reliable-data-center-cooling\/#article","name":"Reliable Data Center Cooling Requires Motor Bearing Protection","headline":"Reliable Data Center Cooling Requires Motor Bearing Protection","author":{"@id":"https:\/\/www.est-aegis.com\/de\/blog\/author\/aegis\/#author"},"publisher":{"@id":"https:\/\/www.est-aegis.com\/de\/#organization"},"image":{"@type":"ImageObject","url":"https:\/\/www.est-aegis.com\/wp-content\/uploads\/dc-applications-300x238-1.jpg","width":300,"height":238,"caption":"#image_title"},"datePublished":"2019-03-05T09:10:51-05:00","dateModified":"2026-10-22T14:52:03-04:00","inLanguage":"de-DE","mainEntityOfPage":{"@id":"https:\/\/www.est-aegis.com\/de\/blog\/reliable-data-center-cooling\/#webpage"},"isPartOf":{"@id":"https:\/\/www.est-aegis.com\/de\/blog\/reliable-data-center-cooling\/#webpage"},"articleSection":"Applications &amp; Industries, Optional"},{"@type":"BreadcrumbList","@id":"https:\/\/www.est-aegis.com\/de\/blog\/reliable-data-center-cooling\/#breadcrumblist","itemListElement":[{"@type":"ListItem","@id":"https:\/\/www.est-aegis.com\/de\/#listItem","position":1,"name":"Home","item":"https:\/\/www.est-aegis.com\/de\/","nextItem":{"@type":"ListItem","@id":"https:\/\/www.est-aegis.com\/de\/blog\/category\/applications-and-industries\/#listItem","name":"Applications &amp; Industries"}},{"@type":"ListItem","@id":"https:\/\/www.est-aegis.com\/de\/blog\/category\/applications-and-industries\/#listItem","position":2,"name":"Applications &amp; Industries","item":"https:\/\/www.est-aegis.com\/de\/blog\/category\/applications-and-industries\/","nextItem":{"@type":"ListItem","@id":"https:\/\/www.est-aegis.com\/de\/blog\/reliable-data-center-cooling\/#listItem","name":"Reliable Data Center Cooling Requires Motor Bearing Protection"},"previousItem":{"@type":"ListItem","@id":"https:\/\/www.est-aegis.com\/de\/#listItem","name":"Home"}},{"@type":"ListItem","@id":"https:\/\/www.est-aegis.com\/de\/blog\/reliable-data-center-cooling\/#listItem","position":3,"name":"Reliable Data Center Cooling Requires Motor Bearing Protection","previousItem":{"@type":"ListItem","@id":"https:\/\/www.est-aegis.com\/de\/blog\/category\/applications-and-industries\/#listItem","name":"Applications &amp; Industries"}}]},{"@type":"Organization","@id":"https:\/\/www.est-aegis.com\/de\/#organization","name":"Electro Static Technology","url":"https:\/\/www.est-aegis.com\/de\/","logo":{"@type":"ImageObject","url":"https:\/\/www.est-aegis.com\/wp-content\/uploads\/logo-aegis-1.svg","@id":"https:\/\/www.est-aegis.com\/de\/blog\/reliable-data-center-cooling\/#organizationLogo","width":244,"height":73,"caption":"aegis logo"},"image":{"@id":"https:\/\/www.est-aegis.com\/de\/blog\/reliable-data-center-cooling\/#organizationLogo"},"sameAs":["https:\/\/x.com\/AEGIS_rings"],"address":{"@id":"https:\/\/www.est-aegis.com\/de\/#postaladdress","@type":"PostalAddress","streetAddress":"31 Winterbrook Road","postalCode":"04256","addressLocality":"Mechanic Falls","addressRegion":"ME","addressCountry":"US"}},{"@type":"Person","@id":"https:\/\/www.est-aegis.com\/de\/blog\/author\/aegis\/#author","url":"https:\/\/www.est-aegis.com\/de\/blog\/author\/aegis\/","name":"AEGIS","image":{"@type":"ImageObject","@id":"https:\/\/www.est-aegis.com\/de\/blog\/reliable-data-center-cooling\/#authorImage","url":"https:\/\/secure.gravatar.com\/avatar\/8df5575541df78c551aa899db7bd2ee11bed27caea7dcd8c7695af230c7c1a04?s=96&d=mm&r=g","width":96,"height":96,"caption":"AEGIS"}},{"@type":"WebPage","@id":"https:\/\/www.est-aegis.com\/de\/blog\/reliable-data-center-cooling\/#webpage","url":"https:\/\/www.est-aegis.com\/de\/blog\/reliable-data-center-cooling\/","name":"Reliable Data Center Cooling Requires Motor Bearing Protection","description":"Variable frequency drives (VFDs) are used in data center cooling, due to the energy savings they offer. But VFDs can cause electrical bearing damage...","inLanguage":"de-DE","isPartOf":{"@id":"https:\/\/www.est-aegis.com\/de\/#website"},"breadcrumb":{"@id":"https:\/\/www.est-aegis.com\/de\/blog\/reliable-data-center-cooling\/#breadcrumblist"},"author":{"@id":"https:\/\/www.est-aegis.com\/de\/blog\/author\/aegis\/#author"},"creator":{"@id":"https:\/\/www.est-aegis.com\/de\/blog\/author\/aegis\/#author"},"image":{"@type":"ImageObject","url":"https:\/\/www.est-aegis.com\/wp-content\/uploads\/dc-applications-300x238-1.jpg","@id":"https:\/\/www.est-aegis.com\/de\/blog\/reliable-data-center-cooling\/#mainImage","width":300,"height":238,"caption":"#image_title"},"primaryImageOfPage":{"@id":"https:\/\/www.est-aegis.com\/de\/blog\/reliable-data-center-cooling\/#mainImage"},"datePublished":"2019-03-05T09:10:51-05:00","dateModified":"2026-10-22T14:52:03-04:00"},{"@type":"WebSite","@id":"https:\/\/www.est-aegis.com\/de\/#website","url":"https:\/\/www.est-aegis.com\/de\/","name":"Electro Static Technology","inLanguage":"de-DE","publisher":{"@id":"https:\/\/www.est-aegis.com\/de\/#organization"}}]},"og:locale":"de_DE","og:site_name":"Electro Static Technology","og:type":"article","og:title":"Reliable Data Center Cooling Requires Motor Bearing Protection","og:description":"Variable frequency drives (VFDs) are used in data center cooling, due to the energy savings they offer. But VFDs can cause electrical bearing damage...","og:url":"https:\/\/www.est-aegis.com\/de\/blog\/reliable-data-center-cooling\/","og:image":"https:\/\/www.est-aegis.com\/wp-content\/uploads\/dc-applications-300x238-1.jpg","og:image:secure_url":"https:\/\/www.est-aegis.com\/wp-content\/uploads\/dc-applications-300x238-1.jpg","og:image:width":300,"og:image:height":238,"article:published_time":"2019-03-05T14:10:51+00:00","article:modified_time":"2026-10-22T18:52:03+00:00","twitter:card":"summary_large_image","twitter:site":"@AEGIS_rings","twitter:title":"Reliable Data Center Cooling Requires Motor Bearing Protection","twitter:description":"Variable frequency drives (VFDs) are used in data center cooling, due to the energy savings they offer. But VFDs can cause electrical bearing damage...","twitter:creator":"@AEGIS_rings","twitter:image":"https:\/\/www.est-aegis.com\/wp-content\/uploads\/dc-applications-300x238-1.jpg","twitter:label1":"Verfasst von","twitter:data1":"AEGIS","twitter:label2":"Gesch\u00e4tzte Lesedauer","twitter:data2":"3 Minuten"},"aioseo_meta_data":{"post_id":"10189","title":"Reliable Data Center Cooling Requires Motor Bearing Protection","description":"Variable frequency drives (VFDs) are used in data center cooling, due to the energy savings they offer. But VFDs can cause electrical bearing damage...","keywords":null,"keyphrases":null,"primary_term":null,"canonical_url":null,"og_title":null,"og_description":null,"og_object_type":"default","og_image_type":"default","og_image_url":null,"og_image_width":null,"og_image_height":null,"og_image_custom_url":null,"og_image_custom_fields":null,"og_video":null,"og_custom_url":null,"og_article_section":null,"og_article_tags":null,"twitter_use_og":false,"twitter_card":"default","twitter_image_type":"default","twitter_image_url":null,"twitter_image_custom_url":null,"twitter_image_custom_fields":null,"twitter_title":null,"twitter_description":null,"schema":{"blockGraphs":[],"customGraphs":[],"default":{"data":{"Article":[],"Course":[],"Dataset":[],"FAQPage":[],"Movie":[],"Person":[],"Product":[],"ProductReview":[],"Car":[],"Recipe":[],"Service":[],"SoftwareApplication":[],"WebPage":[]},"graphName":"","isEnabled":true},"graphs":[]},"schema_type":"default","schema_type_options":null,"pillar_content":false,"robots_default":true,"robots_noindex":false,"robots_noarchive":false,"robots_nosnippet":false,"robots_nofollow":false,"robots_noimageindex":false,"robots_noodp":false,"robots_notranslate":false,"robots_max_snippet":null,"robots_max_videopreview":null,"robots_max_imagepreview":"large","priority":null,"frequency":null,"local_seo":null,"seo_analyzer_scan_date":"2026-10-28 18:30:11","breadcrumb_settings":null,"limit_modified_date":false,"reviewed_by":null,"open_ai":null,"ai":null,"created":"2026-10-22 16:14:08","updated":"2026-11-16 21:32:34","focus_keyword":null,"additional_keywords":null,"truseo_locale":null},"aioseo_breadcrumb":"<div class=\"aioseo-breadcrumbs\"><span class=\"aioseo-breadcrumb\">\n\t<a href=\"https:\/\/www.est-aegis.com\/de\/\" title=\"Home\">Home<\/a>\n<\/span><span class=\"aioseo-breadcrumb-separator\">\u00bb<\/span><span class=\"aioseo-breadcrumb\">\n\t<a href=\"https:\/\/www.est-aegis.com\/de\/blog\/category\/applications-and-industries\/\" title=\"Applications &amp; Industries\">Applications &amp; Industries<\/a>\n<\/span><span class=\"aioseo-breadcrumb-separator\">\u00bb<\/span><span class=\"aioseo-breadcrumb\">\n\tReliable Data Center Cooling Requires Motor Bearing Protection\n<\/span><\/div>","aioseo_breadcrumb_json":[{"label":"Home","link":"https:\/\/www.est-aegis.com\/de\/"},{"label":"Applications &amp; Industries","link":"https:\/\/www.est-aegis.com\/de\/blog\/category\/applications-and-industries\/"},{"label":"Reliable Data Center Cooling Requires Motor Bearing Protection","link":"https:\/\/www.est-aegis.com\/de\/blog\/reliable-data-center-cooling\/"}],"jetpack_featured_media_url":"https:\/\/www.est-aegis.com\/wp-content\/uploads\/dc-applications-300x238-1.jpg","_links":{"self":[{"href":"https:\/\/www.est-aegis.com\/de\/wp-json\/wp\/v2\/posts\/10189","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.est-aegis.com\/de\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.est-aegis.com\/de\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.est-aegis.com\/de\/wp-json\/wp\/v2\/users\/7"}],"replies":[{"embeddable":true,"href":"https:\/\/www.est-aegis.com\/de\/wp-json\/wp\/v2\/comments?post=10189"}],"version-history":[{"count":2,"href":"https:\/\/www.est-aegis.com\/de\/wp-json\/wp\/v2\/posts\/10189\/revisions"}],"predecessor-version":[{"id":10565,"href":"https:\/\/www.est-aegis.com\/de\/wp-json\/wp\/v2\/posts\/10189\/revisions\/10565"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.est-aegis.com\/de\/wp-json\/wp\/v2\/media\/1192"}],"wp:attachment":[{"href":"https:\/\/www.est-aegis.com\/de\/wp-json\/wp\/v2\/media?parent=10189"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.est-aegis.com\/de\/wp-json\/wp\/v2\/categories?post=10189"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.est-aegis.com\/de\/wp-json\/wp\/v2\/tags?post=10189"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}