{"id":10160,"date":"2022-06-01T10:00:00","date_gmt":"2022-06-01T14:00:00","guid":{"rendered":"https:\/\/www.est-aegis.com\/?p=69"},"modified":"2026-10-22T15:00:56","modified_gmt":"2026-10-22T19:00:56","slug":"electrical-bearing-protection-qa-part-24","status":"publish","type":"post","link":"https:\/\/www.est-aegis.com\/fr\/blog\/electrical-bearing-protection-qa-part-24\/","title":{"rendered":"Electrical Bearing Protection Q&#038;A &#8211; Part 24"},"content":{"rendered":"\n<p class=\"wp-block-paragraph\">Q1.\u00a0 Everyone agrees that the VFD is the cause of the common mode voltage that causes capacitive discharge current through the bearings, and the goal of shaft grounding is to create a safe path for current to flow back to the drive.\u00a0 With this in mind, if you use a proper VFD cable, would you bond the ring to the cable screen gland for the shortest path back to the drive, or would you still bond the motor to the surrounding structure?<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">A1.<span style=\"font-weight: normal;\">\u00a0 There are two separate ideas here:\u00a0 First, you are absolutely right that the point of shaft grounding is to give current a non-destructive path back to the bearings.\u00a0 That&rsquo;s why you should use proper VFD cable, <a href=\"\/proper-grounding-is-vital-for-motors-on-drives?hsLang=en-us\" rel=\"noopener\" style=\"font-weight: bold;\">as we have discussed recently<\/a>.\u00a0 But bearing protection pales in comparison to life safety.\u00a0 The motor must be bonded to the facility ground for safety.\u00a0 If a fault occurred in the motor such that a winding shorted to the frame, the VFD cable might not be able to carry all of that current.\u00a0 So you need the motor grounded in the usual way.<img decoding=\"async\" class=\"alignright\" alt=\"vfdcable\" src=\"https:\/\/www.est-aegis.com\/wp-content\/uploads\/vfdcable.jpg\" width=\"350\"><\/span><\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><span style=\"font-weight: normal;\">Bonding a grounding ring directly to the mesh in a VFD cable is unnecessary.\u00a0 When the grounding ring is just bonded to the motor frame, current can move freely between the motor shaft and frame.\u00a0 From there, as you said, it wants to get back to the drive.\u00a0 There are at least two paths:\u00a0 Through the VFD cable directly back to the VFD, through the motor&rsquo;s ground connection, through the building&rsquo;s steel frame, and then back to the drive.\u00a0 Which path will the current take?\u00a0 All of them!<br><\/span><\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><span style=\"font-weight: normal;\">Electric current always splits and takes all available paths, in inverse proportion to their impedance (or resistance, for dc).\u00a0 The mesh inside a VFD cable is specifically designed to have low impedance to high-frequency current.\u00a0 Most likely, the return path through the cable will have lower inductance than any possible path through the building&rsquo;s ground system.\u00a0 So the lion&rsquo;s share of this current will go directly back to the drive through the cable, rather than wandering through the facility, interfering with other systems.\u00a0 This is why it&rsquo;s so important to use high-quality VFD cable.<\/span><\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Q2.\u00a0 I have heard that if the drive is closer than 20&prime; (6m) to the motor, shaft grounding is not necessary.\u00a0 Is that true?<\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><span style=\"font-weight: normal;\"><span style=\"font-weight: bold;\">A2.<\/span> VFD manufacturers say you should keep the drive within 100-150 feet (30-46m).\u00a0 At higher distances, you get reflected voltage waves.\u00a0 Voltage reflection can double the voltage level at the motor terminals.\u00a0 This idea is shown in the figure:\u00a0 The blue wave is voltage coming from the VFD, moving right, and the green wave is reflected voltage, moving left.\u00a0 The red wave is their sum: the total voltage at each point in the cable. (The voltage coming from a drive is a square wave, not a sine wave as shown here, but a square wave can be treated as a sum of many sine waves of different frequencies.\u00a0 We show only one frequency here for clarity.)<\/span><span style=\"font-weight: normal;\"><img decoding=\"async\" class=\"alignright\" alt=\"640px-Standing_wave_SWR_4_(forward,_reflected)_open\" src=\"https:\/\/www.est-aegis.com\/wp-content\/uploads\/640px-Standing_wave_SWR_4_forward2c_reflected_open.gif\" width=\"350\"><\/span><span style=\"font-weight: normal;\"><\/span><\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><span style=\"font-weight: normal;\">Voltage reflection has two consequences.\u00a0 First, it can burn up the motor windings, and second, it makes for higher shaft voltage.\u00a0 Higher shaft voltage means you have more energy available to discharge through the bearings.\u00a0 So more damage per arc, and damage builds up faster.<\/span><span style=\"font-weight: normal;\"><\/span><\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><span style=\"font-weight: normal;\">So large distances are bad, but as far as bearing safety goes, shorter distances aren&rsquo;t necessarily safe.\u00a0 Under 100&prime;, you don&rsquo;t get voltage doubling, but the voltage doesn&rsquo;t change much whether you&rsquo;ve got 90&prime; or only one foot between the motor and drive.\u00a0 Even without voltage doubling, your average motor-drive system has plenty of shaft voltage available to damage the bearings.\u00a0 <\/span><\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><span style=\"font-weight: normal;\">If you ever see us at a <a href=\"https:\/\/www.est-aegis.com\/about\/tradeshows\/\" rel=\"noopener\" style=\"font-weight: bold;\">tradeshow<\/a>, we have demo motor tables with a 1 hp motor and a drive mounted right next to it.\u00a0 You can&rsquo;t fit your hand between the two.\u00a0 But as soon as you turn the system on, you can look at the shaft voltage on an oscilloscope and see discharge occurring.<\/span><span style=\"font-weight: normal;\"><\/span><\/p>\n\n\n\n<p class=\"wp-block-paragraph\">AEGIS Shaft Grounding Rings come with a<span>\u00a0<\/span><a href=\"https:\/\/www.est-aegis.com\/product\/extended-warranty\/\" rel=\"noopener\">2-year extended warranty<\/a><span>\u00a0<\/span>against bearing fluting damage.\u00a0 No other form shaft grounding offers a warranty like this.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">To learn more about AEGIS shaft grounding and best practices for electrical bearing protection,<span>\u00a0<\/span><a href=\"https:\/\/www.est-aegis.com\/resources\/training\/\" rel=\"noopener\">sign up for a training<\/a>.\u00a0 We offer monthly live training webinars, and \u2013 pandemic restrictions permitting \u2013 we can also visit your facility to review your exact application.<\/p>\n\n\n\n<div class=\"wp-block-buttons is-content-justification-center is-layout-flex wp-container-core-buttons-is-layout-fe48e5de wp-block-buttons-is-layout-flex\">\n<div class=\"wp-block-button\"><a class=\"wp-block-button__link wp-element-button\" href=\"https:\/\/www.est-aegis.com\/resources\/training\/\">Sign Up For Training<\/a><\/div>\n<\/div>\n\n","protected":false},"excerpt":{"rendered":"<p>We answer questions about VFD cable and safety cable, and what happens when motors are too far from their drives.<\/p>\n","protected":false},"author":7,"featured_media":1004,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"_acf_changed":false,"content-type":"","_relevanssi_hide_post":"","_relevanssi_hide_content":"","_relevanssi_pin_for_all":"","_relevanssi_pin_keywords":"","_relevanssi_unpin_keywords":"","_relevanssi_related_keywords":"","_relevanssi_related_include_ids":"","_relevanssi_related_exclude_ids":"","_relevanssi_related_no_append":"","_relevanssi_related_not_related":"","_relevanssi_related_posts":"","_relevanssi_noindex_reason":"","footnotes":""},"categories":[1063],"tags":[],"class_list":["post-10160","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-qa-series"],"acf":[],"aioseo_notices":[],"aioseo_head":"\n\t\t<!-- All in One SEO Pro 5.0.5.1 - aioseo.com -->\n\t<meta name=\"description\" content=\"We answer questions about VFD cable and safety cable, and what happens when motors are too far from their drives.\" \/>\n\t<meta name=\"robots\" content=\"noindex, max-snippet:-1, max-image-preview:large, max-video-preview:-1\" \/>\n\t<meta name=\"author\" content=\"AEGIS\"\/>\n\t<link rel=\"canonical\" href=\"https:\/\/www.est-aegis.com\/fr\/blog\/electrical-bearing-protection-qa-part-24\/\" \/>\n\t\t<meta name=\"generator\" content=\"All in One SEO Pro (AIOSEO) 5.0.5.1\" \/>\n\t\t<meta property=\"og:locale\" content=\"fr_FR\" \/>\n\t\t<meta property=\"og:site_name\" content=\"Electro Static Technology\" \/>\n\t\t<meta property=\"og:type\" content=\"article\" \/>\n\t\t<meta property=\"og:title\" content=\"VFD and Safety Cable | Electrical Bearing Protection Q&amp;A Part 24\" \/>\n\t\t<meta property=\"og:description\" content=\"We answer questions about VFD cable and safety cable, and what happens when motors are too far from their drives.\" \/>\n\t\t<meta property=\"og:url\" content=\"https:\/\/www.est-aegis.com\/fr\/blog\/electrical-bearing-protection-qa-part-24\/\" \/>\n\t\t<meta property=\"og:image\" content=\"https:\/\/www.est-aegis.com\/wp-content\/uploads\/640px-Standing_wave_SWR_4_forward2c_reflected_open.gif\" \/>\n\t\t<meta property=\"og:image:secure_url\" content=\"https:\/\/www.est-aegis.com\/wp-content\/uploads\/640px-Standing_wave_SWR_4_forward2c_reflected_open.gif\" \/>\n\t\t<meta property=\"og:image:width\" content=\"640\" \/>\n\t\t<meta property=\"og:image:height\" content=\"274\" \/>\n\t\t<meta property=\"article:published_time\" content=\"2022-06-01T14:00:00+00:00\" \/>\n\t\t<meta property=\"article:modified_time\" content=\"2026-10-22T19:00:56+00:00\" \/>\n\t\t<meta name=\"twitter:card\" content=\"summary_large_image\" \/>\n\t\t<meta name=\"twitter:site\" content=\"@AEGIS_rings\" \/>\n\t\t<meta name=\"twitter:title\" content=\"VFD and Safety Cable | Electrical Bearing Protection Q&amp;A Part 24\" \/>\n\t\t<meta name=\"twitter:description\" content=\"We answer questions about VFD cable and safety cable, and what happens when motors are too far from their drives.\" \/>\n\t\t<meta name=\"twitter:creator\" content=\"@AEGIS_rings\" \/>\n\t\t<meta name=\"twitter:image\" content=\"https:\/\/www.est-aegis.com\/wp-content\/uploads\/640px-Standing_wave_SWR_4_forward2c_reflected_open.gif\" \/>\n\t\t<meta name=\"twitter:label1\" content=\"\u00c9crit par\" \/>\n\t\t<meta name=\"twitter:data1\" content=\"AEGIS\" \/>\n\t\t<meta name=\"twitter:label2\" content=\"Estimation du temps de lecture\" \/>\n\t\t<meta name=\"twitter:data2\" content=\"4 minutes\" \/>\n\t\t<script type=\"application\/ld+json\" class=\"aioseo-schema\">\n\t\t\t{\"@context\":\"https:\\\/\\\/schema.org\",\"@graph\":[{\"@type\":\"Article\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/blog\\\/electrical-bearing-protection-qa-part-24\\\/#article\",\"name\":\"VFD and Safety Cable | Electrical Bearing Protection Q&A Part 24\",\"headline\":\"Electrical Bearing Protection Q&#038;A &#8211; Part 24\",\"author\":{\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/blog\\\/author\\\/aegis\\\/#author\"},\"publisher\":{\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/#organization\"},\"image\":{\"@type\":\"ImageObject\",\"url\":\"https:\\\/\\\/www.est-aegis.com\\\/wp-content\\\/uploads\\\/640px-Standing_wave_SWR_4_forward2c_reflected_open.gif\",\"width\":640,\"height\":274,\"caption\":\"#image_title\"},\"datePublished\":\"2022-06-01T10:00:00-04:00\",\"dateModified\":\"2026-10-22T15:00:56-04:00\",\"inLanguage\":\"fr-FR\",\"mainEntityOfPage\":{\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/blog\\\/electrical-bearing-protection-qa-part-24\\\/#webpage\"},\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/blog\\\/electrical-bearing-protection-qa-part-24\\\/#webpage\"},\"articleSection\":\"Q&amp;A Series, Optional\"},{\"@type\":\"BreadcrumbList\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/blog\\\/electrical-bearing-protection-qa-part-24\\\/#breadcrumblist\",\"itemListElement\":[{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/#listItem\",\"position\":1,\"name\":\"Home\",\"item\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/\",\"nextItem\":{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/blog\\\/category\\\/qa-series\\\/#listItem\",\"name\":\"Q&amp;A Series\"}},{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/blog\\\/category\\\/qa-series\\\/#listItem\",\"position\":2,\"name\":\"Q&amp;A Series\",\"item\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/blog\\\/category\\\/qa-series\\\/\",\"nextItem\":{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/blog\\\/electrical-bearing-protection-qa-part-24\\\/#listItem\",\"name\":\"Electrical Bearing Protection Q&#038;A &#8211; Part 24\"},\"previousItem\":{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/#listItem\",\"name\":\"Home\"}},{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/blog\\\/electrical-bearing-protection-qa-part-24\\\/#listItem\",\"position\":3,\"name\":\"Electrical Bearing Protection Q&#038;A &#8211; Part 24\",\"previousItem\":{\"@type\":\"ListItem\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/blog\\\/category\\\/qa-series\\\/#listItem\",\"name\":\"Q&amp;A Series\"}}]},{\"@type\":\"Organization\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/#organization\",\"name\":\"Electro Static Technology\",\"url\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/\",\"logo\":{\"@type\":\"ImageObject\",\"url\":\"https:\\\/\\\/www.est-aegis.com\\\/wp-content\\\/uploads\\\/logo-aegis-1.svg\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/blog\\\/electrical-bearing-protection-qa-part-24\\\/#organizationLogo\",\"width\":244,\"height\":73,\"caption\":\"aegis logo\"},\"image\":{\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/blog\\\/electrical-bearing-protection-qa-part-24\\\/#organizationLogo\"},\"sameAs\":[\"https:\\\/\\\/x.com\\\/AEGIS_rings\"],\"address\":{\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/#postaladdress\",\"@type\":\"PostalAddress\",\"streetAddress\":\"31 Winterbrook Road\",\"postalCode\":\"04256\",\"addressLocality\":\"Mechanic Falls\",\"addressRegion\":\"ME\",\"addressCountry\":\"US\"}},{\"@type\":\"Person\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/blog\\\/author\\\/aegis\\\/#author\",\"url\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/blog\\\/author\\\/aegis\\\/\",\"name\":\"AEGIS\",\"image\":{\"@type\":\"ImageObject\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/blog\\\/electrical-bearing-protection-qa-part-24\\\/#authorImage\",\"url\":\"https:\\\/\\\/secure.gravatar.com\\\/avatar\\\/8df5575541df78c551aa899db7bd2ee11bed27caea7dcd8c7695af230c7c1a04?s=96&d=mm&r=g\",\"width\":96,\"height\":96,\"caption\":\"AEGIS\"}},{\"@type\":\"WebPage\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/blog\\\/electrical-bearing-protection-qa-part-24\\\/#webpage\",\"url\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/blog\\\/electrical-bearing-protection-qa-part-24\\\/\",\"name\":\"VFD and Safety Cable | Electrical Bearing Protection Q&A Part 24\",\"description\":\"We answer questions about VFD cable and safety cable, and what happens when motors are too far from their drives.\",\"inLanguage\":\"fr-FR\",\"isPartOf\":{\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/#website\"},\"breadcrumb\":{\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/blog\\\/electrical-bearing-protection-qa-part-24\\\/#breadcrumblist\"},\"author\":{\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/blog\\\/author\\\/aegis\\\/#author\"},\"creator\":{\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/blog\\\/author\\\/aegis\\\/#author\"},\"image\":{\"@type\":\"ImageObject\",\"url\":\"https:\\\/\\\/www.est-aegis.com\\\/wp-content\\\/uploads\\\/640px-Standing_wave_SWR_4_forward2c_reflected_open.gif\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/blog\\\/electrical-bearing-protection-qa-part-24\\\/#mainImage\",\"width\":640,\"height\":274,\"caption\":\"#image_title\"},\"primaryImageOfPage\":{\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/blog\\\/electrical-bearing-protection-qa-part-24\\\/#mainImage\"},\"datePublished\":\"2022-06-01T10:00:00-04:00\",\"dateModified\":\"2026-10-22T15:00:56-04:00\"},{\"@type\":\"WebSite\",\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/#website\",\"url\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/\",\"name\":\"Electro Static Technology\",\"inLanguage\":\"fr-FR\",\"publisher\":{\"@id\":\"https:\\\/\\\/www.est-aegis.com\\\/fr\\\/#organization\"}}]}\n\t\t<\/script>\n\t\t<!-- All in One SEO Pro -->\r\n\t\t<title>VFD and Safety Cable | Electrical Bearing Protection Q&amp;A Part 24<\/title>\n\n","aioseo_head_json":{"title":"VFD and Safety Cable | Electrical Bearing Protection Q&A Part 24","description":"We answer questions about VFD cable and safety cable, and what happens when motors are too far from their drives.","canonical_url":"https:\/\/www.est-aegis.com\/fr\/blog\/electrical-bearing-protection-qa-part-24\/","robots":"noindex, max-snippet:-1, max-image-preview:large, max-video-preview:-1","keywords":"","webmasterTools":{"miscellaneous":""},"schema":{"@context":"https:\/\/schema.org","@graph":[{"@type":"Article","@id":"https:\/\/www.est-aegis.com\/fr\/blog\/electrical-bearing-protection-qa-part-24\/#article","name":"VFD and Safety Cable | Electrical Bearing Protection Q&A Part 24","headline":"Electrical Bearing Protection Q&#038;A &#8211; Part 24","author":{"@id":"https:\/\/www.est-aegis.com\/fr\/blog\/author\/aegis\/#author"},"publisher":{"@id":"https:\/\/www.est-aegis.com\/fr\/#organization"},"image":{"@type":"ImageObject","url":"https:\/\/www.est-aegis.com\/wp-content\/uploads\/640px-Standing_wave_SWR_4_forward2c_reflected_open.gif","width":640,"height":274,"caption":"#image_title"},"datePublished":"2022-06-01T10:00:00-04:00","dateModified":"2026-10-22T15:00:56-04:00","inLanguage":"fr-FR","mainEntityOfPage":{"@id":"https:\/\/www.est-aegis.com\/fr\/blog\/electrical-bearing-protection-qa-part-24\/#webpage"},"isPartOf":{"@id":"https:\/\/www.est-aegis.com\/fr\/blog\/electrical-bearing-protection-qa-part-24\/#webpage"},"articleSection":"Q&amp;A Series, Optional"},{"@type":"BreadcrumbList","@id":"https:\/\/www.est-aegis.com\/fr\/blog\/electrical-bearing-protection-qa-part-24\/#breadcrumblist","itemListElement":[{"@type":"ListItem","@id":"https:\/\/www.est-aegis.com\/fr\/#listItem","position":1,"name":"Home","item":"https:\/\/www.est-aegis.com\/fr\/","nextItem":{"@type":"ListItem","@id":"https:\/\/www.est-aegis.com\/fr\/blog\/category\/qa-series\/#listItem","name":"Q&amp;A Series"}},{"@type":"ListItem","@id":"https:\/\/www.est-aegis.com\/fr\/blog\/category\/qa-series\/#listItem","position":2,"name":"Q&amp;A Series","item":"https:\/\/www.est-aegis.com\/fr\/blog\/category\/qa-series\/","nextItem":{"@type":"ListItem","@id":"https:\/\/www.est-aegis.com\/fr\/blog\/electrical-bearing-protection-qa-part-24\/#listItem","name":"Electrical Bearing Protection Q&#038;A &#8211; Part 24"},"previousItem":{"@type":"ListItem","@id":"https:\/\/www.est-aegis.com\/fr\/#listItem","name":"Home"}},{"@type":"ListItem","@id":"https:\/\/www.est-aegis.com\/fr\/blog\/electrical-bearing-protection-qa-part-24\/#listItem","position":3,"name":"Electrical Bearing Protection Q&#038;A &#8211; Part 24","previousItem":{"@type":"ListItem","@id":"https:\/\/www.est-aegis.com\/fr\/blog\/category\/qa-series\/#listItem","name":"Q&amp;A Series"}}]},{"@type":"Organization","@id":"https:\/\/www.est-aegis.com\/fr\/#organization","name":"Electro Static Technology","url":"https:\/\/www.est-aegis.com\/fr\/","logo":{"@type":"ImageObject","url":"https:\/\/www.est-aegis.com\/wp-content\/uploads\/logo-aegis-1.svg","@id":"https:\/\/www.est-aegis.com\/fr\/blog\/electrical-bearing-protection-qa-part-24\/#organizationLogo","width":244,"height":73,"caption":"aegis logo"},"image":{"@id":"https:\/\/www.est-aegis.com\/fr\/blog\/electrical-bearing-protection-qa-part-24\/#organizationLogo"},"sameAs":["https:\/\/x.com\/AEGIS_rings"],"address":{"@id":"https:\/\/www.est-aegis.com\/fr\/#postaladdress","@type":"PostalAddress","streetAddress":"31 Winterbrook Road","postalCode":"04256","addressLocality":"Mechanic Falls","addressRegion":"ME","addressCountry":"US"}},{"@type":"Person","@id":"https:\/\/www.est-aegis.com\/fr\/blog\/author\/aegis\/#author","url":"https:\/\/www.est-aegis.com\/fr\/blog\/author\/aegis\/","name":"AEGIS","image":{"@type":"ImageObject","@id":"https:\/\/www.est-aegis.com\/fr\/blog\/electrical-bearing-protection-qa-part-24\/#authorImage","url":"https:\/\/secure.gravatar.com\/avatar\/8df5575541df78c551aa899db7bd2ee11bed27caea7dcd8c7695af230c7c1a04?s=96&d=mm&r=g","width":96,"height":96,"caption":"AEGIS"}},{"@type":"WebPage","@id":"https:\/\/www.est-aegis.com\/fr\/blog\/electrical-bearing-protection-qa-part-24\/#webpage","url":"https:\/\/www.est-aegis.com\/fr\/blog\/electrical-bearing-protection-qa-part-24\/","name":"VFD and Safety Cable | Electrical Bearing Protection Q&A Part 24","description":"We answer questions about VFD cable and safety cable, and what happens when motors are too far from their drives.","inLanguage":"fr-FR","isPartOf":{"@id":"https:\/\/www.est-aegis.com\/fr\/#website"},"breadcrumb":{"@id":"https:\/\/www.est-aegis.com\/fr\/blog\/electrical-bearing-protection-qa-part-24\/#breadcrumblist"},"author":{"@id":"https:\/\/www.est-aegis.com\/fr\/blog\/author\/aegis\/#author"},"creator":{"@id":"https:\/\/www.est-aegis.com\/fr\/blog\/author\/aegis\/#author"},"image":{"@type":"ImageObject","url":"https:\/\/www.est-aegis.com\/wp-content\/uploads\/640px-Standing_wave_SWR_4_forward2c_reflected_open.gif","@id":"https:\/\/www.est-aegis.com\/fr\/blog\/electrical-bearing-protection-qa-part-24\/#mainImage","width":640,"height":274,"caption":"#image_title"},"primaryImageOfPage":{"@id":"https:\/\/www.est-aegis.com\/fr\/blog\/electrical-bearing-protection-qa-part-24\/#mainImage"},"datePublished":"2022-06-01T10:00:00-04:00","dateModified":"2026-10-22T15:00:56-04:00"},{"@type":"WebSite","@id":"https:\/\/www.est-aegis.com\/fr\/#website","url":"https:\/\/www.est-aegis.com\/fr\/","name":"Electro Static Technology","inLanguage":"fr-FR","publisher":{"@id":"https:\/\/www.est-aegis.com\/fr\/#organization"}}]},"og:locale":"fr_FR","og:site_name":"Electro Static Technology","og:type":"article","og:title":"VFD and Safety Cable | Electrical Bearing Protection Q&amp;A Part 24","og:description":"We answer questions about VFD cable and safety cable, and what happens when motors are too far from their drives.","og:url":"https:\/\/www.est-aegis.com\/fr\/blog\/electrical-bearing-protection-qa-part-24\/","og:image":"https:\/\/www.est-aegis.com\/wp-content\/uploads\/640px-Standing_wave_SWR_4_forward2c_reflected_open.gif","og:image:secure_url":"https:\/\/www.est-aegis.com\/wp-content\/uploads\/640px-Standing_wave_SWR_4_forward2c_reflected_open.gif","og:image:width":640,"og:image:height":274,"article:published_time":"2022-06-01T14:00:00+00:00","article:modified_time":"2026-10-22T19:00:56+00:00","twitter:card":"summary_large_image","twitter:site":"@AEGIS_rings","twitter:title":"VFD and Safety Cable | Electrical Bearing Protection Q&amp;A Part 24","twitter:description":"We answer questions about VFD cable and safety cable, and what happens when motors are too far from their drives.","twitter:creator":"@AEGIS_rings","twitter:image":"https:\/\/www.est-aegis.com\/wp-content\/uploads\/640px-Standing_wave_SWR_4_forward2c_reflected_open.gif","twitter:label1":"\u00c9crit par","twitter:data1":"AEGIS","twitter:label2":"Estimation du temps de lecture","twitter:data2":"4 minutes"},"aioseo_meta_data":{"post_id":"10160","title":"VFD and Safety Cable | Electrical Bearing Protection Q&A Part 24","description":"We answer questions about VFD cable and safety cable, and what happens when motors are too far from their drives.","keywords":null,"keyphrases":null,"primary_term":null,"canonical_url":null,"og_title":null,"og_description":null,"og_object_type":"default","og_image_type":"default","og_image_url":null,"og_image_width":null,"og_image_height":null,"og_image_custom_url":null,"og_image_custom_fields":null,"og_video":null,"og_custom_url":null,"og_article_section":null,"og_article_tags":null,"twitter_use_og":false,"twitter_card":"default","twitter_image_type":"default","twitter_image_url":null,"twitter_image_custom_url":null,"twitter_image_custom_fields":null,"twitter_title":null,"twitter_description":null,"schema":{"blockGraphs":[],"customGraphs":[],"default":{"data":{"Article":[],"Course":[],"Dataset":[],"FAQPage":[],"Movie":[],"Person":[],"Product":[],"ProductReview":[],"Car":[],"Recipe":[],"Service":[],"SoftwareApplication":[],"WebPage":[]},"graphName":"","isEnabled":true},"graphs":[]},"schema_type":"default","schema_type_options":null,"pillar_content":false,"robots_default":true,"robots_noindex":false,"robots_noarchive":false,"robots_nosnippet":false,"robots_nofollow":false,"robots_noimageindex":false,"robots_noodp":false,"robots_notranslate":false,"robots_max_snippet":null,"robots_max_videopreview":null,"robots_max_imagepreview":"large","priority":null,"frequency":null,"local_seo":null,"seo_analyzer_scan_date":"2026-10-28 18:23:50","breadcrumb_settings":null,"limit_modified_date":false,"reviewed_by":null,"open_ai":null,"ai":null,"created":"2026-10-22 16:13:46","updated":"2026-11-16 21:27:11","focus_keyword":null,"additional_keywords":null,"truseo_locale":null},"aioseo_breadcrumb":"<div class=\"aioseo-breadcrumbs\"><span class=\"aioseo-breadcrumb\">\n\t<a href=\"https:\/\/www.est-aegis.com\/fr\/\" title=\"Home\">Home<\/a>\n<\/span><span class=\"aioseo-breadcrumb-separator\">\u00bb<\/span><span class=\"aioseo-breadcrumb\">\n\t<a href=\"https:\/\/www.est-aegis.com\/fr\/blog\/category\/qa-series\/\" title=\"Q&amp;A Series\">Q&amp;A Series<\/a>\n<\/span><span class=\"aioseo-breadcrumb-separator\">\u00bb<\/span><span class=\"aioseo-breadcrumb\">\n\tElectrical Bearing Protection Q&amp;A \u2013 Part 24\n<\/span><\/div>","aioseo_breadcrumb_json":[{"label":"Home","link":"https:\/\/www.est-aegis.com\/fr\/"},{"label":"Q&amp;A Series","link":"https:\/\/www.est-aegis.com\/fr\/blog\/category\/qa-series\/"},{"label":"Electrical Bearing Protection Q&#038;A &#8211; Part 24","link":"https:\/\/www.est-aegis.com\/fr\/blog\/electrical-bearing-protection-qa-part-24\/"}],"jetpack_featured_media_url":"https:\/\/www.est-aegis.com\/wp-content\/uploads\/640px-Standing_wave_SWR_4_forward2c_reflected_open.gif","_links":{"self":[{"href":"https:\/\/www.est-aegis.com\/fr\/wp-json\/wp\/v2\/posts\/10160","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/www.est-aegis.com\/fr\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/www.est-aegis.com\/fr\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/www.est-aegis.com\/fr\/wp-json\/wp\/v2\/users\/7"}],"replies":[{"embeddable":true,"href":"https:\/\/www.est-aegis.com\/fr\/wp-json\/wp\/v2\/comments?post=10160"}],"version-history":[{"count":3,"href":"https:\/\/www.est-aegis.com\/fr\/wp-json\/wp\/v2\/posts\/10160\/revisions"}],"predecessor-version":[{"id":10701,"href":"https:\/\/www.est-aegis.com\/fr\/wp-json\/wp\/v2\/posts\/10160\/revisions\/10701"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/www.est-aegis.com\/fr\/wp-json\/wp\/v2\/media\/1004"}],"wp:attachment":[{"href":"https:\/\/www.est-aegis.com\/fr\/wp-json\/wp\/v2\/media?parent=10160"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/www.est-aegis.com\/fr\/wp-json\/wp\/v2\/categories?post=10160"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/www.est-aegis.com\/fr\/wp-json\/wp\/v2\/tags?post=10160"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}